Inspector
will verify code compliance by assuring that a minimum size #8 solid
copper conductor is attached to the pool steel shell. Proper connectors
are used for all bond wire connections; all connections are tight and
correctly made. # 8 solid copper is attached to the rear exterior of the
pool light wet niche. Internal wet niche bond is secure and proper
encapsulating compound is used to completely cover termination of # 8
insulated wire. Metal within 5’ of waters edge is connected to the
equipotential bonding grid, and a # 8 solid copper conductor is run
completely around pool walk area between 18” and 24” from waters edge
and 4” to 6” below grade.
Final
Inspector will verify code compliance to assure proper
wiring from main panel to pool equipment panel. Proper bonding of associated
water circulating equipment for pool. Proper pool light junction box, if used,
and proper bonding and sealing. Height of junction box or pool transformer. GFI
protected receptacle between 10’ and 20’ from waters edge. Verify height limits
on luminaries above high water level. Proper bonding of screen enclosure.